X
+970-2-2422931 | info@nextwave.ps

Tescom 300(100-300KVA)

Tescom 300 series are, True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.


• Output isolation transformer
• Up to 91% efficiency
• Static by-pass
• LCD front panel
• 128 events alarm memory (4000 alarms)
• RS232 and relay contacts
• Custom input and output voltage ranges
• SNMP compatible communication
• T-MON remote monitoring software
• Parralel operation up to 4 devices
• High performance at nonlinear loads
• Custom input voltage and frequency ranges
• 2 years warranty
• 10 years spare parts support
• Manufactured according to EC Directive; EN62040


MODEL

3100

3120

3160

3200

3250

3300

Power (kVA)

100

120

160

200

250

300

INPUT

Voltage

380/400 VAC 3P + N + G  ± 15%

By-pass voltage

380/400 VAC 3P + N  ± 10%

Input frequency

50Hz (60Hz on request)   ± 5%

OUTPUT

Power (kW)

80

96

128

160

200

240

Power factor

0,8

Voltage

380/400 VAC 3P + N 

Voltage stability

Balanced load: ± 1%, Unbalanced load: ± 2%, Step load: ± 5%

Voltage recovery time

After step load: max. 25ms

Frequency

50Hz (60Hz on request)

Frequency tolerance

 

Line synchronized: ± 2% , free running: ± 0,2% 

Efficiency (at 100% load) 

90-92%

Crest factor

 

3:1

Overload protection

100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass

Short circuit protection

Electronic short circuit protection

Voltage THD

Linear load: < 3%

Non linear load: < 5%

BATTERIES

Type

Sealed Lead Acid - Maintenance Free

Number of batteries

30

32

Float charging voltage

405 VDC

432 VDC

End of discharge voltage

300 VDC

320 VDC

Battery ambient temperature

25ºC

Battery protection

Automatic circuit breaker

Battery test

Automatic every 72 hours

GENERAL

Standards

EN 62040-1,EN62040-2

Serial communication

Dry contacts & RS232

Software

T-Mon UPS Management Software (3 clients, +1 server management std.)

Temperature range

0ºC - 40ºC

Ventilation

Forced air cooling

Relative humidity 

< %90 (non-condensing)

Protection degree

IP20

Altitude

< 2000m above sea level

Acoustic noise 

65 dBA

70 dBA

Weight without batteries (kg)

750

765

802

970

1328

1370

Dimensions (mm) HxWxD

1650x1110x810

1730x1195x870

1880x1565x925

OPTIONS

Different input / output voltage

Please ask 

Input transformer

Galvanic isolation transformer at the input (in external cabinet)

Input THD

10% (with 12 Pulse or 18 Pulse rectifier, according to UPS range)

5% (with 18 Pulse rectifier, + filter), up to 100kVA

Input power factor

0,95 - 0,98 (with 18 Pulse rectifier)

Adaptors

SNMP, MODBUS, Remote Mon. Panel, RS485

Parallel operation

N + 1 (up to 4 units)

(*):

In 18Pulse & 12Pulse applications, the standard chassis dimensions may change.